R-503 Other names and brand names: CFC-503, Freon-503 Genetron-503, Forane-503 Freon is a registered trade name for E. I. DuPont. Genetron is a registered trade name for Allied Signal Corporation. Forane is a registered trade name for Elf Atochem. |
|
General Information
Chemical Formula | CAS Registry # | Color & Odor | Refrigerant Applications |
Azeotropic Blend of R-13 and R-23 | 75-46-7 and 75-72-9 | Colorless Pressurized liquid with slight ether like odor | Very low temperature refrigeration |
Physical Data
Molecular Mass | Boiling Point C° | Boiling Point F° | Critical Temperature C° | Critical Temperature F° | Critical Pressure MPa | Critical Pressure psia |
87.25 | -87.5 | -125.5 | 18.4 | 65.1 | 4.27 | 619 |
Toxicity & Global Warming Data
TLV-TWA |
Years of Atmospheric Lifetime |
Ozone Depletion Potential |
Global Warming Potential |
1,000 |
|
0.599 |
14300 |
Packaging Information
Packaged in |
Volumes available in pounds |
Color of Container |
Pressurized cylinders |
5, 9, 20, 80 |
Blue-green (aqua) |
Shipping Information
DOT Shipping Name |
Hazard Class |
UN/NA Number |
Packing Group |
Labels Required |
Chlorotrifluoromethane and trifluoromethane azeotropic mixture |
2.2 |
UN2599 |
|
nonflammable gas |
ARI 700 Reclaim Standards
Allowable Comp. Weight % |
Air and other non-condensables % by volume @ 25°C |
Water in ppm by weight |
All other impurities including refrigerants as % by weight |
Oil and other high boiling residues as % by volume |
Particulates/solids visually clean to pass |
Acidity as ppm by weight |
Chloride (pass/fail is 3 ppm) |
39.0-41.0 |
1.5 |
10 |
0.50 |
0.01 |
pass |
1.0 |
pass |
Alternative Refrigerant Option for
R-13 Chillers
(Alternative will require retrofit and maybe new
equipment)
Alternative | Composition | Manufacturers | Trade Names |
HFC-23 | N/A | DuPont | SUVA 23 |
R-508 | HFC-23 R-116 (C2F6) |
DuPont ICI Americas |
SUVA-95 KLEA 508 |
SUVA is a registered trade name for E. I.
DuPont
KLEA is a registered trade name for ICI Americas
THE DATA PRESENTED
ON THIS DATASHEET HAS BEEN COLLATED FROM A NUMBER OF SOURCES. THE DATA HAS NOT BEEN
VALIDATED. USE THIS DATA AT YOUR OWN DISCRETION - REFRIGERANT SUPPLY INC. DOES NOT
GUARANTEE ITS ACCURACY, OR ITS APPLICABILITY TO ANY PURPOSE.
Refrigerant Supply Inc provides
this information in its website as a free value to anyone who cares about
environmental or chemical issues. The sources of this information could not be
validated. This site is a compilation of information meant for casual reference
only. Refrigerant Supply Inc. assumes no liability whatsoever for the accuracy
or use of the information offered. It is hoped that this resource provides users
with a heightened interest in such matters, stimulating independent research and
review. Any matters which need professional attention may be brought to our
attention via Email. All rights reserved Refrigerant Supply Inc. 1999 |